Motor Data Identification Selection / Motid Selection - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Note
The following applies to permanent-magnet synchronous motors:
Without de-selection in bit 11, in the closed-loop control mode, the direct inductance LD and the quadrature inductance
Lq are measured at a low current.
When de-selecting with bit 11 or in the U/f mode, the stator inductance is measured at half the rated motor current.
If the stator is inductance is not measured but is to be estimated, then bit 0 should be set and bit 11 should be de-
selected.
For bit 19 = 1:
All parameters are automatically saved after a successful motor data identification.
If a speed controller optimization run is then selected, the parameters are only saved after this measurement has been
completed.
For bit 21 = 1:
The converter output voltage measurement is calibrated at the start of the motor data identification.
p1910

Motor data identification selection / MotID selection

Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Sets the motor data identification routine.
The motor data identification routine is carried out after the next switch-on command.
p1910 = 1:
All motor data and the drive converter characteristics are identified and then transferred to the following parameters:
p0350, p0354, p0356, p0357, p0358, p0360, p1825, p1828, p1829, p1830
After this, the control parameter p0340 = 3 is automatically calculated.
p1910 = 20:
Only for internal SIEMENS use.
Value:
0:
1:
2:
20:
21:
22:
23:
24:
25:
26:
27:
28:
Dependency:
"Quick commissioning" must be carried out (p0010 = 1, p3900 > 0) before executing the motor data identification
routine!
When selecting the motor data identification routine, the drive data set changeover is suppressed.
See also: p1900
See also: F07990, A07991
NOTICE
After the motor data identification (p1910 > 0) has been selected, alarm A07991 is output and a motor data
identification routine is carried out as follows at the next switch-on command:
- current flows through the motor and a voltage is present at the drive converter output terminals.
- during the identification routine, the motor shaft can rotate through a maximum of half a revolution.
- however, no torque torque is generated.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Inhibited
Complete identification (ID) and acceptance of motor data
Complete identification (ID) of motor data without acceptance
Voltage vector input
Voltage vector input without filter
Rectangular voltage vector input without filter
Triangular voltage vector input without filter
Rectangular voltage vector input with filter
Triangular voltage vector input with filter
Enter voltage vector with DTC correction
Enter voltage vector with AVC
Enter voltage vector with DTC + AVC correction
Calculated: -
Scaling: -
Unit selection: -
Max:
28
Parameters
7.3 Parameters
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0
545