Rtc Time / Rtc Time; Rtc Date / Rtc Date - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

p8400[0...2]

RTC time / RTC time

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0
Description:
Sets and displays the time on the real-time clock in hours, minutes, and seconds.
The time is stored in the internal clock block in the drive and continues to run even if the supply voltage for the Control
Unit is interrupted (for approx. 5 days).
Index:
[0] = Hour (0 ... 23)
[1] = Minute (0 ... 59)
[2] = Second (0 ... 59)
Note
The time from p8400 and p8401 is used to display the fault and alarm times.
When displaying the fault time and alarm time, the switchover to daylight saving time is not taken into account.
The parameter is not reset when the factory setting is restored (p0010 = 30, p0970).
The time is entered and displayed in 24-hour format.
RTC: Real-time clock
p8401[0...2]

RTC date / RTC date

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0
Description:
Sets and displays the date on the real-time clock in year, month, and day.
The date is stored in the internal clock block in the drive and continues to run even if the supply voltage for the Control
Unit is interrupted (for approx. 5 days).
Recommendation:
When the date is set as an index, the day should always be written last because, if a date is invalid, the day is always
corrected to the last valid day in that particular month of the year.
Index:
[0] = Day (1 ... 31)
[1] = Month (1 ... 12)
[2] = Year (YYYY)
Note
The time from p8400 and p8401 is used to display the fault and alarm times.
When displaying the fault time and alarm time, the switchover to daylight saving time is not taken into account.
The parameter is not reset when the factory setting is restored (p0010 = 30, p0970).
RTC: Real-time clock
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: -
Unit selection: -
Max:
59
Calculated: -
Scaling: -
Unit selection: -
Max:
9999
Parameters
7.3 Parameters
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
0
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
[0] 1
[1] 1
[2] 1970
671