Technology Controller Ramp-Up/Ramp-Down Time / Tec_Ctr T_Ru/Rd; Co: Technology Controller Output Signal / Tec_Ctrl Outp_Sig; Co: Technology Controller Output Scaling / Tec_Ctrl Outp Scal; Ci: Technology Controller Output Scaling / Tec_Ctrl Outp Scal - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Parameters
7.3 Parameters
p2293

Technology controller ramp-up/ramp-down time / Tec_ctr t_RU/RD

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.00 [s]
Description:
Sets the ramping time for the output signal of the technology controller.
Dependency:
See also: p2291, p2292
Note
The time refers to the set maximum and minimum limits (p2291, p2292).
r2294

CO: Technology controller output signal / Tec_ctrl outp_sig

Access level: 2
Can be changed: -
Unit group: -
Min:
- [%]
Description:
Display and connector output for the output signal of the technology controller.
Dependency:
See also: p2295
p2295

CO: Technology controller output scaling / Tec_ctrl outp scal

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-100.00 [%]
Description:
Sets the scaling for the output signal of the technology controller.
p2296[0...n]

CI: Technology controller output scaling / Tec_ctrl outp scal

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the signal source for the scaling value of the technology controller.
Dependency:
See also: p2295
p2297[0...n]
CI: Technology controller maximum limit signal source / Tec_ctrMaxLimS_src
Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the signal source for the maximum limiting of the technology controller.
Dependency:
See also: p2291
618
Calculated: -
Scaling: -
Unit selection: -
Max:
100.00 [s]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
- [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
100.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
-
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7958
Factory setting:
1.00 [s]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7958
Factory setting:
- [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7958
Factory setting:
100.00 [%]
Data type: Unsigned32 /
FloatingPoint32
Dynamic index: CDS, p0170
Function diagram: 7958
Factory setting:
2295[0]
Data type: Unsigned32 /
FloatingPoint32
Dynamic index: CDS, p0170
Function diagram: 7958
Factory setting:
1084[0]
SINAMICS G120XA converter

Advertisement

Table of Contents
loading