Usb Memory Access / Usb Mem Acc; Safely Remove Memory Card / Mem_Card Rem; Co/Bo: Safely Remove Memory Card Status / Mem_Card Rem Stat - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Parameters
7.3 Parameters
p8991

USB memory access / USB mem acc

Access level: 3
Can be changed: T
Unit group: -
Min:
1
Description:
Selects the storage medium for access via the USB mass storage.
Value:
1:
2:
Note
A change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
p9400

Safely remove memory card / Mem_card rem

Access level: 2
Can be changed: T
Unit group: -
Min:
0
Description:
Setting and display when memory card is "removed safely".
Procedure:
Setting p9400 = 2 results in a value of 3
--> The memory card can be removed safely. After removal the value sets itself to 0 automatically.
Setting p9400 = 2 results in a value of 100
--> The memory card cannot be removed safely. Removal may destroy the file system on the memory card. It may be
necessary to set p9400 = 2 again.
Value:
0:
1:
2:
3:
100:
Dependency:
See also: r9401
NOTICE
Removing the memory card without a request (p9400 = 2) and confirmation (p9400 = 3) may destroy the file system
on the memory card. The memory card will then no longer work properly and must be replaced.
Note
The status when the memory card is being "removed safely" is shown in r9401.
For value = 0, 1, 3, 100:
These values can only be displayed, not set.
r9401.0...3

CO/BO: Safely remove memory card status / Mem_card rem stat

Access level: 2
Can be changed: -
Unit group: -
Min:
-
Description:
Displays the status of the memory card.
Bit field:
Bit
00
682
Memory card
Flash r/w internal
No memory card inserted
Memory card inserted
Request "safe removal" of the memory card
"Safe removal" possible
"Safe removal" not possible due to access
Signal name
Memory card inserted
Calculated: -
Scaling: -
Unit selection: -
Max:
2
Calculated: -
Scaling: -
Unit selection: -
Max:
100
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
1
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
-
0 signal
FP
No
-
SINAMICS G120XA converter

Advertisement

Table of Contents
loading