p0761[0...3]
CU analog inputs wire breakage monitoring response threshold / CU WireBrkThresh
Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.00
Description:
Sets the response threshold for the wire breakage monitoring of the analog inputs.
The unit for the parameter value depends on the set analog input type.
Index:
[0] = AI0 (X131 3/4)
[1] = AI1 (X131 10/11)
[2] = Reserved
[3] = Reserved
Dependency:
For the following analog input type, the wire breakage monitoring is active:
p0756[0...1] = 1 (unipolar voltage input monitored (+2 V ... +10 V)), unit [V]
p0756[0...2] = 3 (unipolar current input monitored (+4 mA ... +20 mA)), unit [mA]
p0756[3]: Wire breakage monitoring is not supported for this analog input.
See also: p0756
Note
AI: Analog Input
When p0761 = 0, wire breakage monitoring is not carried out.
p0762[0...3]
CU analog inputs wire breakage monitoring delay time / CU wire brk t_del
Access level: 3
Can be changed: T, U
Unit group: -
Min:
0 [ms]
Description:
Sets the delay time for the wire breakage monitoring of the analog inputs.
Index:
[0] = AI0 (X131 3/4)
[1] = AI1 (X131 10/11)
[2] = Reserved
[3] = Reserved
Note
AI: Analog Input
p0764[0...3]

CU analog inputs dead zone / CU AI dead zone

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: -
Unit selection: -
Max:
20.00
Calculated: -
Scaling: -
Unit selection: -
Max:
1000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max:
20.000
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9566, 9568
Factory setting:
2.00
Data type: Unsigned16
Dynamic index: -
Function diagram: 9566, 9568
Factory setting:
100 [ms]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 2251
Factory setting:
0.000