Load Monitoring Speed Threshold Value 1 / N_Thresh 1; Load Monitoring Speed Threshold Value 2 / N_Thresh 2; Load Monitoring Speed Threshold Value 3 / N_Thresh 3 - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Note
The response to the faults F07923 ... F07925 can be set.
This parameter setting has no effect on the generation of fault F07936.
p2181 = 7, 8 can only be combined with p2193 = 4, 5.
p2182[0...n]

Load monitoring speed threshold value 1 / n_thresh 1

Access level: 3
Can be changed: T, U
Unit group: 3_1
Min:
0.00 [rpm]
Description:
Sets the speed/torque envelope curve for load monitoring.
The envelope curve (upper and lower envelope curve) is defined as follows based on 3 speed thresholds:
p2182 (n_threshold 1) --> p2185 (M_threshold 1, upper), p2186 (M_threshold 1, lower)
p2183 (n_threshold 2) --> p2187 (M_threshold 2, upper), p2188 (M_threshold 2, lower)
p2184 (n_threshold 3) --> p2189 (M_threshold 3, upper), p2190 (M_threshold 3, lower)
Dependency:
The following applies: p2182 < p2183 < p2184
See also: p2183, p2184, p2185, p2186
See also: A07926
Note
In order that the load monitoring can reliably respond, the speed threshold p2182 should always be set lower than the
minimum motor speed to be monitored.
p2183[0...n]

Load monitoring speed threshold value 2 / n_thresh 2

Access level: 3
Can be changed: T, U
Unit group: 3_1
Min:
0.00 [rpm]
Description:
Sets the speed/torque envelope curve for load monitoring.
The envelope curve (upper and lower envelope curve) is defined as follows based on 3 speed thresholds:
p2182 (n_threshold 1) --> p2185 (M_threshold 1, upper), p2186 (M_threshold 1, lower)
p2183 (n_threshold 2) --> p2187 (M_threshold 2, upper), p2188 (M_threshold 2, lower)
p2184 (n_threshold 3) --> p2189 (M_threshold 3, upper), p2190 (M_threshold 3, lower)
Dependency:
The following applies: p2182 < p2183 < p2184
See also: p2182, p2184, p2187, p2188
See also: A07926
p2184[0...n]

Load monitoring speed threshold value 3 / n_thresh 3

Access level: 3
Can be changed: T, U
Unit group: 3_1
Min:
0.00 [rpm]
Description:
Sets the speed/torque envelope curve for load monitoring.
The envelope curve (upper and lower envelope curve) is defined as follows based on 3 speed thresholds:
p2182 (n_threshold 1) --> p2185 (M_threshold 1, upper), p2186 (M_threshold 1, lower)
p2183 (n_threshold 2) --> p2187 (M_threshold 2, upper), p2188 (M_threshold 2, lower)
p2184 (n_threshold 3) --> p2189 (M_threshold 3, upper), p2190 (M_threshold 3, lower)
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: -
Unit selection: p0505
Max:
210000.00 [rpm]
Calculated: -
Scaling: -
Unit selection: p0505
Max:
210000.00 [rpm]
Calculated: -
Scaling: -
Unit selection: p0505
Max:
210000.00 [rpm]
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 8013
Factory setting:
150.00 [rpm]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 8013
Factory setting:
900.00 [rpm]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 8013
Factory setting:
1500.00 [rpm]
597