Parameters
7.3 Parameters
p2306

Technology controller system deviation inversion / Tec_ctr SysDev inv

Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Setting to invert the system deviation of the technology controller.
The setting depends on the type of control loop.
Value:
0:
1:
CAUTION
If the actual value inversion is incorrectly selected, then the closed-loop control with the technology controller can
become unstable and can oscillate!
Note
The correct setting can be determined as follows:
- inhibit the technology controller (p2200 = 0).
- increase the motor speed and in so doing, measure the actual value signal (of the technology controller).
- if the actual value increases with increasing motor speed, then the inversion should be switched out.
- if the actual value decreases with increasing motor speed, then the inversion should be set.
If value = 0:
The drive reduces the output speed when the actual value rises (e.g. for heating fans, intake pump, compressor).
If value = 1:
The drive increases the output speed when the actual value increases (e.g. for cooling fans, discharge pumps).
p2310
CI: Technology controller Kp adaptation input value signal source / Kp adapt inp s_src
Access level: 2
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source for the input value of the adaptation of proportional gain Kp for the technology controller.
Dependency:
See also: p2252, p2311, p2312, p2313, p2314, p2315, r2316
p2311

Technology controller Kp adaptation lower value / Kp adapt lower val

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000
Description:
Sets the lower value for the adaptation of proportional gain Kp for the technology controller.
Dependency:
See also: p2310, p2312, p2313, p2314, p2315, r2316
CAUTION
The upper value must be set higher than the lower value (p2312 > p2311).
Note
Kp adaptation is activated with p2252.7 = 1.
620
No inversion
Inversion
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
1000.000
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: Integer16
Dynamic index: -
Function diagram: 7958
Factory setting:
0
Data type: Unsigned32 /
FloatingPoint32
Dynamic index: -
Function diagram: 7959
Factory setting:
0
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7959
Factory setting:
1.000
SINAMICS G120XA converter