Skip Speed Bandwidth / N_Skip Bandwidth; Ci: Minimum Speed Signal Source / N_Min S_Src; Bi: Inhibit Negative Direction / Inhib Neg Dir; Bi: Inhibit Positive Direction / Inhib Pos Dir - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Parameters
7.3 Parameters
p1101[0...n]

Skip speed bandwidth / n_skip bandwidth

Access level: 3
Can be changed: T, U
Unit group: 3_1
Min:
0.000 [rpm]
Description:
Sets the bandwidth for the skip speeds/velocities 1 to 4.
Dependency:
See also: p1091, p1092, p1093, p1094
Note
The setpoint (reference) speeds are skipped (suppressed) in the range of the skip speed +/-p1101.
Steady-state operation is not possible in the skipped (suppressed) speed range. The skip (suppression) range is
skipped.
Example:
p1091 = 600 and p1101 = 20
--> setpoint speeds between 580 and 620 [rpm] are skipped.
For the skip bandwidths, the following hysteresis behavior applies:
For a setpoint speed coming from below, the following applies:
r1170 < 580 [rpm] and 580 [rpm] <= r1114 <= 620 [rpm] --> r1119 = 580 [rpm]
For a setpoint speed coming from above, the following applies:
r1170 > 620 [rpm] and 580 [rpm] <= r1114 <= 620 [rpm] --> r1119 = 620 [rpm]
p1106[0...n]

CI: Minimum speed signal source / n_min s_src

Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source for lowest possible motor speed.
Dependency:
See also: p1080
NOTICE
The effective minimum speed is formed from p1080 and p1106.
p1110[0...n]

BI: Inhibit negative direction / Inhib neg dir

Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source to disable the negative direction.
Dependency:
See also: p1111
p1111[0...n]

BI: Inhibit positive direction / Inhib pos dir

Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source to disable the positive direction.
Dependency:
See also: p1110
480
Calculated: -
Scaling: p2000
Unit selection: p0505
Max:
210000.000 [rpm]
Calculated: -
Scaling: p2000
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 3050
Factory setting:
0.000 [rpm]
Data type: Unsigned32 /
FloatingPoint32
Dynamic index: CDS, p0170
Function diagram: 3050
Factory setting:
0
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2505, 3040
Factory setting:
1
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2505, 3040
Factory setting:
0