Parameters
7.3 Parameters
p8420[0...6]

RTC DTC2 weekday of activation / RTC DTC2 day act

Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Sets the weekday on which timer 2 is activated (DTC2).
The switch-on/off time is set in p8421/p8422 and the result displayed via binector output r8423.
Value:
0:
1:
Index:
[0] = Monday
[1] = Tuesday
[2] = Wednesday
[3] = Thursday
[4] = Friday
[5] = Saturday
[6] = Sunday
Dependency:
See also: p8409, p8421, p8422, r8423
NOTICE
This parameter can only be changed when p8409 = 0.
Note
DTC: Digital Time Clock (timer)
RTC: Real-time clock
p8421[0...1]

RTC DTC2 switch-on time / RTC DTC2 t_ON

Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Sets the switch on time in hours and minutes for time switch 2 (DTC2).
BO: r8423 = 1 signal:
The condition for the set weekday (p8420) and switch-on time has been fulfilled.
Index:
[0] = Hour (0 ... 23)
[1] = Minute (0 ... 59)
Dependency:
See also: p8409, p8420, r8423
NOTICE
This parameter can only be changed when p8409 = 0.
Note
DTC: Digital Time Clock (timer)
RTC: Real-time clock
p8422[0...1]

RTC DTC2 off time / RTC DTC2 t_OFF

Access level: 3
Can be changed: T
Unit group: -
Min:
0
676
Weekday deactivated
Weekday activated
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Calculated: -
Scaling: -
Unit selection: -
Max:
59
Calculated: -
Scaling: -
Unit selection: -
Max:
59
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
0
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
0