Co: Actual Speed Smoothed Signals / N_Act Smth Message; Current Threshold Value / I_Thres; Current Threshold Value Reached Delay Time / I_Thresh Rch T_Del; Dc Link Voltage Threshold Value / Vdc Thresh Val - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Parameters
7.3 Parameters
r2169

CO: Actual speed smoothed signals / n_act smth message

Access level: 2
Can be changed: -
Unit group: 3_1
Min:
- [rpm]
Description:
Display and connector output of the smoothed speed actual value for messages.
Dependency:
See also: p2153
p2170[0...n]

Current threshold value / I_thres

Access level: 3
Can be changed: T, U
Unit group: 6_2
Min:
0.00 [Arms]
Description:
Sets the absolute current threshold for the messages.
"I_act >= I_threshold p2170" (BO: r2197.8)
"I_act < I_threshold p2170" (BO: r2198.8)
Dependency:
See also: p2171
p2171[0...n]

Current threshold value reached delay time / I_thresh rch t_del

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0 [ms]
Description:
Sets the delay time for the comparison of the current actual value (r0068) with the current threshold value (p2170).
Dependency:
See also: p2170
p2172[0...n]

DC link voltage threshold value / Vdc thresh val

Access level: 3
Can be changed: T, U
Unit group: 5_2
Min:
0 [V]
Description:
Sets the DC link voltage threshold value for the following messages:
"Vdc_act <= Vdc_threshold p2172" (BO: r2197.9)
"Vdc_act > Vdc_threshold p2172" (BO: r2197.10)
Dependency:
See also: p2173
p2173[0...n]
DC link voltage comparison delay time / t_del Vdc
Access level: 3
Can be changed: T, U
Unit group: -
Min:
0 [ms]
Description:
Sets the delay time for the comparison of the DC link voltage r0070 with the threshold value p2172.
Dependency:
See also: p2172
594
Calculated: -
Scaling: p2000
Unit selection: p0505
Max:
- [rpm]
Calculated:
CALC_MOD_LIM_REF
Scaling: p2002
Unit selection: p0505
Max:
10000.00 [Arms]
Calculated: -
Scaling: -
Unit selection: -
Max:
10000 [ms]
Calculated: -
Scaling: p2001
Unit selection: p0505
Max:
2000 [V]
Calculated: -
Scaling: -
Unit selection: -
Max:
10000 [ms]
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 8010
Factory setting:
- [rpm]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 8022
Factory setting:
0.00 [Arms]
Data type: Unsigned16
Dynamic index: DDS, p0180
Function diagram: 8022
Factory setting:
10 [ms]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
800 [V]
Data type: Unsigned16
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
10 [ms]