p2024[0...2]

Fieldbus interface times / Fieldbus times

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0 [ms]
Description:
Sets the time values for the fieldbus interface.
For Modbus the following applies:
p2024[0, 1]: Not relevant.
p2024[2]: Telegram pause time (pause time between two telegrams).
The following applies for BACnet:
p2024[0]: APDU timeout.
p2024[1, 2]: Not relevant.
Index:
[0] = Max. processing time
[1] = Character delay time
[2] = Telegram pause time
Dependency:
See also: p2020, p2030
Note
For p2024[2] (Modbus):
If the field bus baud rate is changed (p2020), the default time setting is restored.
The default setting corresponds to a time of 3.5 characters (dependent on the baud rate that has been set).
p2025[0...4]

Fieldbus interface BACnet settings / BACnet setting

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0
Description:
Sets the parameter for communication via BACnet.
p2025[0]:
Device object instance number (0 ... 4194303).
p2025[1]:
Maximum number of info frames (1 ... 10).
p2025[2]:
Number of APDU retries (0 ... 39).
p2025[3]:
Maximum master address (1 ... 127).
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
PKW 4 words
PKW variable
Calculated: -
Scaling: -
Unit selection: -
Max:
10000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max:
4194303
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9310
Factory setting:
[0] 6000 [ms]
[1] 0 [ms]
[2] 0 [ms]
Data type: Unsigned32
Dynamic index: -
Function diagram: 9310
Factory setting:
[0] 1
[1] 5
[2] 3
[3] 32
[4] 0