Deragging Forward Time / Derag Fw Time; Deragging Reverse Time / Derag Rev Tim; Number Of Deragging Cycles / Derag Cycs; Pipe Filling Enable / Pf En - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Parameters
7.3 Parameters
p29596[0...n]

Deragging forward time / Derag fw time

Access level: 3
Can be changed: T
Unit group: -
Min:
0.00 [s]
Description:
Defines the duration time at each forward speed for deragging.
p29597[0...n]

Deragging reverse time / Derag rev tim

Access level: 3
Can be changed: T
Unit group: -
Min:
0.00 [s]
Description:
Defines the duration time at reverse speed for deragging.
p29598[0...n]

Number of deragging cycles / Derag cycs

Access level: 3
Can be changed: T
Unit group: -
Min:
1
Description:
The number of the deragging cycle is repeated
p29610[0...n]

Pipe filling enable / PF En

Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Enable the pipe filling function.
Value:
0:
1:
Note
The pipe filling function allows the inverter to fill an empty pipe slowly when the inverter works for the first time after each
power-up.
p29611[0...n]
Pipe filling mode / PF mode
Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Selects the mode for pipe filling.
Value:
0:
1:
716
The pipe filling function is disabled
The pipe filling function is enabled
The pipe is filled based on specified time
The pipe is filled based on the actual pressure feedback
Calculated: -
Scaling: -
Unit selection: -
Max:
1000.00 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
1000.00 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
999
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
5.00 [s]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
5.00 [s]
Data type: Unsigned32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
1
Data type: Integer16
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
0
Data type: Integer16
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
0
SINAMICS G120XA converter