Setting the hibernation mode

Number
p1080
p1110
p2200
p2251 = 1
p2298
p2398
p2390
p2391
p2392
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Name
Minimum speed
0 (factory setting) ... 19,500 rpm. Lower limit of the motor
speed, independently of the speed target value.
Block negative direction
Parameter to block the negative direction
Technology controller enable
0: Technology controller deactivated (factory setting),
1: Technology controller activated
Technology controller mode
0: Technology controller as main setpoint (factory setting),
1: Technology controller as supplementary setpoint
Technology controller minimum limiting
Parameter for the minimum limiting of the technology con‐
troller
Hibernation mode
0: Hibernation mode inhibited (factory setting)
1: Hibernation mode enabled
Hibernation mode start speed
0 (factory setting) ... 21,000 rpm. As soon as this speed is
fallen below, the hibernation mode delay time starts and
switches off the motor once it expires. The hibernation mode
start speed is calculated as follows:
Start speed = p1080 + p2390
p1080 = minimum speed
p2390 = hibernation mode start speed
Hibernation mode delay time
0 ... 3599 s (factory setting 120). The hibernation mode delay
time starts as soon as the output frequency of the converter
drops below the hibernation mode start speed p2390. If the
output frequency increases above this threshold during the
delay time, the hibernation mode delay time is interrupted.
Otherwise, the motor is switched off after the delay time has
expired (if necessary, after a short boost).
Hibernation mode restart value (as a %)
Is required if the technology controller is used as the main
setpoint.
As soon as the technology controller deviation (r2273) ex‐
ceeds the hibernation restart value, the converter switches to
normal operation and the motor starts up with a setpoint of
1.05 * (p1080 + p2390). As soon as this value is reached, the
motor continues to operate with the setpoint of the technology
controller (r2260).
Advanced commissioning
6.9 Energy saving
Via
Via ex‐
tech.
ternal
setpoint
setpoint
-
-
-
-
-
341