r2145[0...63]

Alarm time received in days / t_alarm recv days

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Displays the system runtime in days when the alarm occurred.
Dependency:
See also: r2110, r2122, r2123, r2124, r2125, r2134, r2146, p8401
NOTICE
The time comprises r2145 (days) and r2123 (milliseconds).
Note
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
r2146[0...63]

Alarm time removed in days / t_alarm res days

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Displays the system runtime in days when the alarm was cleared.
Dependency:
See also: r2110, r2122, r2123, r2124, r2125, r2134, r2145, p8401
NOTICE
The time comprises r2146 (days) and r2125 (milliseconds).
Note
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
p2148[0...n]

BI: RFG active / RFG active

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the signal source for the signal "ramp-function generator active" for the following signals/messages:
"Speed setpoint - actual value deviation within tolerance t_on" (BO: r2199.4)
"Ramp-up/ramp-down completed" (BO: r2199.5)
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note
The binector input is automatically interconnected to r1199.2 as a default setting.
p2149[0...n]

Monitoring configuration / Monit config

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated:
CALC_MOD_LIM_REF
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Parameters
7.3 Parameters
Data type: Unsigned16
Dynamic index: -
Function diagram: 8065
Factory setting:
-
Data type: Unsigned16
Dynamic index: -
Function diagram: 8065
Factory setting:
-
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 8011
Factory setting:
0
Data type: Unsigned16
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
0000 1001 bin
589