Parameters
7.3 Parameters
p1756
Motor model changeover speed hysteresis encoderless operation / MotMod n_chgov hys
Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.0 [%]
Description:
Sets the hysteresis for the changeover speed of the motor model for encoderless operation.
Dependency:
See also: p1755
Note
The parameter value refers to p1755.
Extremely small hystereses can have a negative impact on the stability in the changeover speed range, and very high
hystereses in the standstill range.
p1780[0...n]

Motor model adaptation configuration / MotMod adapt conf

CUG120XA_USS
Access level: 3
(PM330)
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the configuration for the adaptation circuit of the motor model.
Induction motor (ASM):
Rs, Lh and offset compensation.
Bit field:
Bit
01
02
04
07
10
11
Dependency:
In the U/f characteristic operating mode, only bit 7 and bit 11 are relevant.
For active motor model feedback (see p1784), the Lh adaptation is internally deactivated automatically.
Note
When selecting the compensation of the valve interlocking via Rs (bit 7), the compensation in the gating unit is
deactivated and is instead taken into account in the motor model.
In order that the correction values of the Rs and Lh adaptation (selected using bit 0 ... bit 1) are correctly accepted when
changing over the drive data set, a dedicated motor number must be entered into p0826 for each different motor.
ASM: Induction motor
RESM: synchronous reluctance motor
p1800[0...n]

Pulse frequency setpoint / Pulse freq setp

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.500 [kHz]
Description:
Sets the pulse frequency for the converter.
This parameter is pre-set to the rated converter value when the drive is first commissioned.
Dependency:
Minimum pulse frequency: p1800 >= 12 * p1082 * r0313 / 60
See also: p0230
536
Signal name
Select motor model ASM Rs adaptation
Select motor model ASM Lh adaptation
Select motor model offset adaptation
Select T(valve) with Rs adaptation
Filter time combination current like current ctrl integral time Yes
Fast flying restart with voltage model for induction motor
Calculated: CALC_MOD_REG Data type: FloatingPoint32
Scaling: -
Unit selection: -
Max:
95.0 [%]
Calculated: CALC_MOD_CON Data type: Unsigned16
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max:
16.000 [kHz]
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Dynamic index: -
Function diagram: 6730, 6731
Factory setting:
50.0 [%]
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
0000 1000 0001 0100 bin
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 8021
Factory setting:
4.000 [kHz]