Co: Profidrive Pzd Receive Double Word / Pzd Recv Dw; Ci: Profidrive Pzd Send Double Word / Pzd Send Dw - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Dependency:
See also: p2021
NOTICE
The display is updated after switching on, and not cyclically.
r2060[0...10]

CO: PROFIdrive PZD receive double word / PZD recv DW

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Connector output to interconnect PZD (setpoints) with double word format received from the fieldbus controller.
Index:
[0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
[6] = PZD 7 + 8
[7] = PZD 8 + 9
[8] = PZD 9 + 10
[9] = PZD 10 + 11
[10] = PZD 11 + 12
Dependency:
See also: r2050
NOTICE
Where there is a multiple interconnection of a connector output, all the connector inputs must either have Integer or
FloatingPoint data types.
A BICO interconnection for a single PZD can only take place either on r2050 or r2060.
p2061[0...15]

CI: PROFIdrive PZD send double word / PZD send DW

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Selects the PZD (actual values) with double word format to be sent to the fieldbus controller.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: 4000H
Unit selection: -
Max:
-
Calculated: -
Scaling: 4000H
Unit selection: -
Max:
-
Parameters
7.3 Parameters
Data type: Integer32
Dynamic index: -
Function diagram: 2440, 2468
Factory setting:
-
Data type: Unsigned32 /
Integer32
Dynamic index: -
Function diagram: 2470
Factory setting:
0