X132 digital inputs/outputs, analog input

Table 7- 19
Type: Spring-loaded terminal (Page 263)
Max. cross section that can be connected: 1.5 mm
DI/DO: bidirectional digital input/output, AI: analog input; M: Electronics ground
1)
The rapid inputs can be used as inputs for measuring input or as inputs for the external zero mark
2)
The maximum cable length that can be connected is 30 m.
Note
The common mode range may not be violated. This means that the analog differential
voltage signals can have a maximum offset voltage of ±15 V with respect to the reference
potential. If the range is infringed, incorrect results may occur during analog/digital
conversion.
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
X132 bidirectional digital inputs/outputs and analog input
Terminal
Designation
1
DI/DO 8
2
DI/DO 9
3
DI/DO 10
4
DI/DO 11
5
M
6
M
7
AI +
8
AI -
Technical data
1)
As input:
input characteristics in accordance with IEC
61131-2, type 1
All digital inputs are floating. The reference poten-
tial is M.
Typical current consumption: 7 mA at 24 V DC
Level (incl. ripple)
High level: 15 ... 30 V
Low level: -3 ... 5 V
DI 8, 9, 10, and 11 are "rapid inputs"
Signal propagation times:
For "0" → "1": 4 μs
For "1" → "0": approx. 4 μs
As output:
Maximum load current: 100 mA
Max. leakage current: 0.5 mA
Short-circuit protected, automatic restart after
short-circuit
Load types: resistive, capacitive, inductive
Switching frequency:
with inductive load: Max. 0.5 Hz
Maximum lamp load: 2 W
Reference potential for the digital inputs/outputs
and the analog input
Differential input voltage: -10 ... 10 V
Maximum resolution range: -12.5 ... 12.5 V
Common-mode range: -15 ... 15 V
Resolution: 13 bit (referred to max. resolution
range)
2
CU305 Control Units
7.3 Interface description
2)
149