Response For Successful Write Operation; Communication Procedure; Procedure For Communication In A Normal Case; Communication Error - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Table 6-29

Response for successful write operation

Value
Byte
Description
11 h
0
Slave address
06 h
1
Function code (write)
Number of following data bytes (20 h: 32 bytes ≙ 16 registers)
20 h
2
0002 h
3,4
40601: DS47 Control = 2 (request was executed)
2F04 h
5,6
40602: Function code 2F h (47), response length 4 bytes
8002 h
7,8
40603: Request reference mirrored = 80 h,
response identifier = 2 (change parameter)
0101 h
9,10
40604: DO-ID = 1, number of parameters = 1
xx h
11
CRC "Low"
xx h
12
CRC "High"
Table 6-30
Response for unsuccessful write operation - write request still not completed
Value
Byte
Description
11 h
0
Slave address
06 h
1
Function code (write)
Number of following data bytes (20 h: 32 bytes ≙ 16 registers)
20 h
2
0001 h
3,4
40601: DS47 Control = 1 (request is processed)
2F00 h
5,6
40602: Function 2F h(47), response length 0 (fault)
0004 h
7,8
40603: Error code:
issued)
xx h
9
CRC "Low"
xx h
10
CRC "High"
6.2.3.10

Communication procedure

Procedure for communication in a normal case

Normally, the master sends a telegram to a slave (address range 1 ... 247). The slave sends a
response telegram to the master. This response telegram mirrors the function code; the slave
enters its own address in the telegram and so the slave identifies itself with the master.
The slave only processes orders and telegrams which are directly addressed to it.

Communication error

If the slave detects a communication error on receipt (parity, CRC), it does not send a response
to the master (this can lead to "setpoint timeout").
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
0004 Response Not Ready (response has still not been
Advanced commissioning
6.2 Drive control
165