Default setting
Procedure with the BOP-2 operator panel:
→ SETUP → ... → MAc PAr → P15 = X AI PID → ... → FINISH
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Setting Parameter
p0015 = 42
42
AI 0 p2253[0] =
755[0]
p1070[0] =
755[0]
AI 1 p2264[0] =
755[1]
AO 0 p0771[0] = 21
AO 1 p0771[1] = 27
Characteristics
4.2 Control interfaces
Setting Parameter
DI 0
p29652[0] = 722.0
p29650[0] = 0
ON/OFF1
p0840[0] = 29659.0
OFF2
p0844[0] = 29659.1
DI 4
p2200 = 722.4
DI 5
p2104[0] = 722.5
DO 0
p0730 = 52.3
DO 1
p0731 = 52.2
DO 2
p0732 = 52.1
DO 3
p0733 = 52.7