Parameters
7.3 Parameters
p29527

Multi-pump control interlocking time / Mpc t_interl

Access level: 3
Can be changed: T
Unit group: -
Min:
0 [s]
Description:
Interlocking time during which, following the connection or disconnection of a motor, no further motors are connected
or disconnected using the multi-control control. This avoids duplicate switching operations.
p29528

Multi-pump control switch-out speed offset / Mpc sw_out offset

Access level: 3
Can be changed: T, U
Unit group: 3_1
Min:
0.0 [rpm]
Description:
Sets the speed offset which pluses p1080 as the speed threshold.
If the system deviation of the technology controller has exceeded the threshold p29523 for p29525s (or exceeded the
threshold p29526) and the motor has reached the speed threshold p1080+p29528, a motor will be switched out.
r29529.0...7

CO/BO: Multi-pump control status word / Mpc ZSW

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Displays the status word of the multi-pump control
Bit field:
Bit
00
01
02
03
04
05
06
07
p29530[0...3]

Multi-pump control absolute operating hours / Mpc op_hrs

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.00 [h]
Description:
Displays the total operating hours for motors.
The display can only be reset to zero.
Index:
[0] = motor 1 operating hours
[1] = motor 2 operating hours
[2] = motor 3 operating hours
[3] = motor 4 operating hours
708
Signal name
Start motor 1
Start motor 2
Start motor 3
Start motor 4
Switch-in/switch-out active
All motors active
Cycling not possible
Alarm active
Calculated: -
Scaling: -
Unit selection: -
Max:
650 [s]
Calculated: -
Scaling: -
Unit selection: p0505
Max:
21000.0 [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max:
340.28235E36 [h]
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
0 [s]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
100.0 [rpm]
Data type: Unsigned32
Dynamic index: -
Function diagram: -
Factory setting:
-
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
0.00 [h]
SINAMICS G120XA converter

Advertisement

Table of Contents
loading

Table of Contents