Technology Controller Actual Value Filter Time Constant; Co: Technology Controller Actual Value After Filter; Technology Controller Lower Limit Actual Value / Tec_Ctrl L_Lim Act; Technology Controller Gain Actual Value / Tech_Ctrl Gain Act - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Parameters
7.3 Parameters
p2265
Technology controller actual value filter time constant / Tec_ctrl act T
Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the time constant for the actual value filter (PT1) of the technology controller.
r2266
CO: Technology controller actual value after filter / Tec_ctr act aftFlt
Access level: 3
Can be changed: -
Unit group: 9_1
Min:
- [%]
Description:
Display and connector output for the smoothed actual value after the filter (PT1) of the technology controller.
p2267
Technology controller upper limit actual value / Tec_ctrl u_lim act
Access level: 3
Can be changed: T, U
Unit group: 9_1
Min:
-200.00 [%]
Description:
Sets the upper limit for the actual value signal of the technology controller.
Dependency:
See also: p2264, p2265, p2271
See also: F07426
NOTICE
If the actual value exceeds this upper limit, this results in fault F07426.
p2268

Technology controller lower limit actual value / Tec_ctrl l_lim act

Access level: 3
Can be changed: T, U
Unit group: 9_1
Min:
-200.00 [%]
Description:
Sets the lower limit for the actual value signal of the technology controller.
Dependency:
See also: p2264, p2265, p2271
See also: F07426
NOTICE
If the actual value falls below this lower limit, this results in fault F07426.
p2269

Technology controller gain actual value / Tech_ctrl gain act

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.00 [%]
Description:
Sets the scaling factor for the actual value of the technology controller.
Dependency:
See also: p2264, p2265, p2267, p2268, p2271
614
Calculated: -
Scaling: -
Unit selection: -
Max:
60.000 [s]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max:
- [%]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max:
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max:
200.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
500.00 [%]
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7958
Factory setting:
0.000 [s]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7958
Factory setting:
- [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7958
Factory setting:
100.00 [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7958
Factory setting:
-100.00 [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7958
Factory setting:
100.00 [%]
SINAMICS G120XA converter

Advertisement

Table of Contents
loading

Table of Contents