p1082 [rpm]
p1800 [kHz]
For converter FSG with sine-wave filter, operation is only permissible in the vector control
mode.
2.6.4

dv/dt filter plus VPL

A combination of dv/dt filter and a voltage peak limiter (VPL) - dv/dt filter plus VPL - are available
to suppress voltage peaks and enable longer motor cables to be connected.
When using the dv/dt filter plus VPL, observe the following restrictions:
● The maximum output frequency is 150 Hz.
● The maximum pulse frequency is 4 kHz.
Further details for the functional principle and the application cases are available on the Internet
(https://support.industry.siemens.com/cs/ww/en/view/109748645).
Note
dv/dt filters plus VPL are available as optional components for converters of frame sizes FSH
and FSJ.
Article number
Converter variants
Frame size
FSH
FSJ
2.6.5

Operator panel

An operator panel has been designed to enhance the interface and communications
capabilities of the converter. It can be used to commission, troubleshoot and control the
converter, as well as to back up and transfer the converter settings. The operator panels
(BOP-2 and IOP-2) can be mounted either directly on the converter or in a control cabinet door
using a door mounting kit.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
150*60/r0313
4
Maximum permissible motor cable length (Page 64)
Rated power (kW)
315
355
400
450
500
560
150*60/r0313
4
dv/dt filter plus VPL
Article number
6SL3000-2DE38-4AA0
6SL3000-2DE41-4AA0
Description
2.6 Optional components
150*60/r0313
4
35