Bi: Multi-Pump Control Motor Under Repair / Mpc Mtr_Und_Ser; Multi-Pump Control Index Of Motors Under Repair / Mpc Mtr Und Repair; Co/Bo: Multi-Pump Control Bypass Command / Mpc Bypass Cmd; Multi-Pump Control Deviation Threshold / Mpc Devia Thres - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

p29543[0...3]

BI: Multi-pump control motor under repair / Mpc mtr_und_ser

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the signal source(digital input or p29542) for service mode.
The signal indicates the motor/motors which is/are under repair or locked manually.
Index:
[0] = motor 1 under repair
[1] = motor 2 under repair
[2] = motor 3 under repair
[3] = motor 4 under repair
r29544

Multi-pump control index of motors under repair / Mpc mtr und repair

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Displays the motors which are interlocked/under repair.
Value:
r29544.0 = 1: Motor 1 is interlocked / under repair
r29544.1 = 1: Motor 2 is interlocked / under repair
r29544.2 = 1: Motor 3 is interlocked / under repair
r29544.3 = 1: Motor 4 is interlocked / under repair
r29545

CO/BO: Multi-pump control bypass command / Mpc bypass cmd

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Dispalys the signal source for the control command to the bypass.It is BiCo to p1266.
Note
The "Bypass" function switches the motor between inverter and line operation.
p29546

Multi-pump control deviation threshold / Mpc devia thres

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.00 [%]
Description:
If the system deviation (p2273) at the PID technology controller exceeds the threshold (p29546) and no more motor
is available, alarm A52963 occurs.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
100.00 [%]
Parameters
7.3 Parameters
Data type: Unsigned32 / Binary
Dynamic index: -
Function diagram: -
Factory setting:
[0] 29542.0
[1] 29542.1
[2] 29542.2
[3] 29542.3
Data type: Unsigned32
Dynamic index: -
Function diagram: -
Factory setting:
-
Data type: Unsigned32
Dynamic index: -
Function diagram: -
Factory setting:
-
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
20.00 [%]
711

Advertisement

Table of Contents
loading

Table of Contents