p0295

Fan run-on time / Fan run-on time

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0 [s]
Description:
Sets the fan run-on time after the pulses for the power unit have been canceled.
Note
- Under certain circumstances, the fan can continue to run for longer than was set (e.g. as a result of the excessively
high heat sink temperature).
- For values less than 1 s, a 1 s run on time for the fan is active.
- for a PM230 power unit, sizes D - F the parameter is ineffective.
r0296

DC link voltage undervoltage threshold / Vdc U_lower_thresh

Access level: 3
Can be changed: -
Unit group: -
Min:
- [V]
Description:
Threshold to detect a DC link undervoltage.
If the DC link voltage falls below this threshold, the drive unit is tripped due to a DC link undervoltage condition.
Dependency:
See also: F30003
r0297

DC link voltage overvoltage threshold / Vdc U_upper_thresh

Access level: 3
Can be changed: -
Unit group: -
Min:
- [V]
Description:
Threshold to detect a DC link overvoltage.
If the DC link voltage exceeds the threshold specified here, the drive unit is tripped due to DC link overvoltage.
Dependency:
See also: F30002
p0300[0...n]

Motor type selection / Mot type sel

Access level: 2
Can be changed: C2(1, 3)
Unit group: -
Min:
0
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: -
Unit selection: -
Max:
600 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
- [V]
Calculated: -
Scaling: -
Unit selection: -
Max:
- [V]
Calculated: -
Scaling: -
Unit selection: -
Max:
603
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
0 [s]
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
- [V]
Data type: Unsigned16
Dynamic index: -
Function diagram: 8750, 8760,
8850, 8864, 8950, 8964
Factory setting:
- [V]
Data type: Integer16
Dynamic index: MDS, p0130
Function diagram: 6310
Factory setting:
0