Free Tec_Ctrl 0 Actual Value Inversion / Ftec0 Act V Inv; Co: Free Tec_Ctrl 0 Actual Value After Limiter / Ftec0 Act V Af Lim; Co: Free Tec_Ctrl 0 System Deviation / Ftec0 Sys Dev; Free Tec_Ctrl 0 Differentiation Time Constant / Ftec0 D Comp T - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

p11071

Free tec_ctrl 0 actual value inversion / Ftec0 act v inv

Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Sets the inversion of the actual value signal of the free technology controller 0.
Value:
0:
1:
r11072

CO: Free tec_ctrl 0 actual value after limiter / Ftec0 act v af lim

Access level: 2
Can be changed: -
Unit group: 9_2
Min:
- [%]
Description:
Display and connector output for the actual value after the limiter of the free technology controller 0.
r11073

CO: Free tec_ctrl 0 system deviation / Ftec0 sys dev

Access level: 2
Can be changed: -
Unit group: 9_2
Min:
- [%]
Description:
Display and connector output for the system deviation of the free technology controller 0.
p11074

Free tec_ctrl 0 differentiation time constant / Ftec0 D comp T

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the time constant for the differentiation (D component) of the free technology controller 0.
Note
Value = 0: Differentiation is deactivated.
p11080
Free tec_ctrl 0 proportional gain / Ftec0 Kp
Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000
Description:
Sets the proportional gain (P component) of the free technology controller 0.
Note
Value = 0: The proportional gain is deactivated.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
No inversion
Inversion
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Calculated: -
Scaling: PERCENT
Unit selection: p11026
Max:
- [%]
Calculated: -
Scaling: PERCENT
Unit selection: p11026
Max:
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
60.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
1000.000
Parameters
7.3 Parameters
Data type: Integer16
Dynamic index: -
Function diagram: 7030
Factory setting:
0
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7030
Factory setting:
- [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7030
Factory setting:
- [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7030
Factory setting:
0.000 [s]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7030
Factory setting:
1.000
689

Advertisement

Table of Contents
loading

Table of Contents