Write Protection / Write Protection; Write Protection Multi-Master Fieldbus System Access Behavior; Khp Oem Exception List Number Of Indices For P7764 / Khp Oem Qty P7764; Khp Oem Exception List / Khp Oem Excep List - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Parameters
7.3 Parameters
p7761

Write protection / Write protection

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0
Description:
Setting for activating/deactivating the write protection for adjustable parameters.
Value:
0:
1:
Dependency:
See also: r7760
Note
Parameters with the "WRITE_NO_LOCK" attributes are excluded from the write protection.
p7762
Write protection multi-master fieldbus system access behavior / Fieldbus acc_behav
Access level: 3
Can be changed: T, U
Unit group: -
Min:
0
Description:
Sets the behavior for write protection when accessing via multi-master fieldbus systems (e.g. CAN, BACnet).
Value:
0:
1:
Dependency:
See also: r7760, p7761
p7763

KHP OEM exception list number of indices for p7764 / KHP OEM qty p7764

Access level: 3
Can be changed: T, U
Unit group: -
Min:
1
Description:
Sets the number of parameters for the OEM exception list (p7764[0...n]).
p7764[0...n], with n = p7763 - 1
Dependency:
See also: p7764
Note
KHP: Know-How Protection
Even if know-how protection is set, parameters in this list can be read and written to.
p7764[0...n]

KHP OEM exception list / KHP OEM excep list

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0
Description:
OEM exception list (p7764[0...n] for setting parameters that should be excluded from know-how protection.
p7764[0...n], with n = p7763 - 1
Dependency:
The number of indices depends on p7763.
See also: p7763
666
Deactivate write protection
Activate write protection
Write access independent of p7761
Write access dependent on p7761
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Calculated: -
Scaling: -
Unit selection: -
Max:
1
Calculated: -
Scaling: -
Unit selection: -
Max:
500
Calculated: -
Scaling: -
Unit selection: -
Max:
65535
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
1
Data type: Unsigned16
Dynamic index: p7763
Function diagram: -
Factory setting:
[0] 7766
[1...499] 0
SINAMICS G120XA converter