Motor Data Identification Control Word / Motid Stw - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

p1901
Test pulse evaluation configuration / Test puls config
CUG120XA_USS
Access level: 3
(PM330)
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the configuration for the test pulse evaluation.
Bit 00: Check for conductor-to-conductor short circuit once/always when the pulses are enabled.
Bit 01: Check for ground fault once/always when the pulses are enabled.
Bit 02: Activation of the tests selected using bit 00 and/or bit 01 each time the pulses are enabled
Recommendation:
If the ground fault test is incorrectly initiated because the motor is not at a complete standstill, then the pulse
cancellation delay time (p1228) should be increased.
Bit field:
Bit
00
01
02
Dependency:
The ground fault test is only possible when the motor is stationary, and is therefore only realized when flying restart
is deactivated (p1200 = 0).
See also: p0287
Note
If a conductor-to-conductor short-circuit is detected during the test, this is displayed in r1902.1.
If a ground fault is detected during the test, this is displayed in r1902.2.
For bit 02 = 0:
If the test was successful once after POWER ON (see r1902.0), then it is not repeated.
For bit 02 = 1:
The test is not only performed after POWER ON, but also each time the pulses are enabled.
For chassis power units, the ground fault is also determined using the summed output current (see p0287).
p1909[0...n]

Motor data identification control word / MotID STW

Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the configuration for the motor data identification.
Bit field:
Bit
00
02
03
05
06
07
11
12
14
15
16
17
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Signal name
Phase short-circuit test pulse active
Ground fault detection test pulse active
Test pulse at each pulse enable
Signal name
Stator inductance estimate no measurement
Rotor time constant estimate no measurement
Leakage inductance estimate no measurement
Determine Tr and Lsig evaluation in the time range
Activate vibration damping
Deactivate vibration detection
Deactivate pulse measurement Lq Ld
Deactivate rotor resistance Rr measurement
Deactivate valve interlocking time measurement
Determine only stator resistance, valve voltage fault, dead
time
Short motor identification (lower quality)
Measurement without control parameter calculation
Calculated: CALC_MOD_ALL Data type: Unsigned32
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Calculated: CALC_MOD_ALL Data type: Unsigned32
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Parameters
7.3 Parameters
Dynamic index: -
Function diagram: -
Factory setting:
0000 bin
0 signal
FP
No
-
No
-
No
-
Dynamic index: MDS, p0130
Function diagram: -
Factory setting:
0000 0000 0000 0000 0000
0000 0000 0000 bin
0 signal
FP
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
-
543