Figure 6-47
The converter calculates the parameters of the PID controller from the determined oscillation
frequency.
Executing autotuning
1. Select with p2350 the appropriate controller setting.
2. Switch on the motor.
The converter signals Alarm A07444.
3. Wait until alarm A07444 goes away.
The converter has recalculated parameters p2280, p2274 and p2285.
If the converter signals fault F07445:
– If possible, double p2354 and p2355.
– Repeat the autotuning with the changed parameters.
4. Back up the calculated values so that they are protected against power failure, e.g. using the
BOP‑2: OPTIONS → RAM‑ROM.
You have auto tuned the PID controller.
❒
Parameters
Number
p2274
p2280
p2285
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Example for speed setpoint and actual process value for autotuning
Name
Technology controller differentiation time constant
Technology controller proportional gain
Technology controller integral time
Advanced commissioning
6.5 Technology controller
Factory setting
0.0 s
See parameter list
See parameter list