Parameters
7.3 Parameters
r0070

CO: Actual DC link voltage / Vdc act val

Access level: 3
Can be changed: -
Unit group: 5_2
Min:
- [V]
Description:
Display and connector output for the measured actual value of the DC link voltage.
Dependency:
See also: r0026
NOTICE
When measuring a DC link voltage < 200 V, for the Power Module (e.g. PM240) a valid measured value is not supplied.
In this case, when an external 24 V power supply is connected, a value of approx. 24 V is displayed in the display
parameter.
Note
The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
r0071

Maximum output voltage / Voltage max

Access level: 3
Can be changed: -
Unit group: 5_1
Min:
- [Vrms]
Description:
Displays the maximum output voltage.
Dependency:
The maximum output voltage depends on the actual DC link voltage (r0070) and the maximum modulation depth
(p1803).
Note
As the (driven) motor load increases, the maximum output voltage drops as a result of the reduction in DC link voltage.
r0072

CO: Output voltage / U_output

Access level: 3
Can be changed: -
Unit group: 5_1
Min:
- [Vrms]
Description:
Display and connector output for the actual output voltage of the power unit.
Dependency:
See also: r0025
Note
The output voltage is available smoothed (r0025) and unsmoothed (r0072).
r0075

CO: Current setpoint field-generating / Id_set

Access level: 3
Can be changed: -
Unit group: 6_2
Min:
- [Arms]
372
Calculated: -
Scaling: p2001
Unit selection: p0505
Max:
- [V]
Calculated: -
Scaling: p2001
Unit selection: p0505
Max:
- [Vrms]
Calculated: -
Scaling: p2001
Unit selection: p0505
Max:
- [Vrms]
Calculated: -
Scaling: p2002
Unit selection: p0505
Max:
- [Arms]
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6723, 6724,
6730, 6731, 6799
Factory setting:
- [V]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6301, 6640,
6700, 6722, 6723, 6724, 6725,
6727
Factory setting:
- [Vrms]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 5700, 6730,
6731, 6799
Factory setting:
- [Vrms]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 6700, 6714,
6725
Factory setting:
- [Arms]