7.3 Parameters
p1967

Speed_ctrl_opt dynamic factor / n_opt dyn_factor

Access level: 3
Can be changed: T, U
Unit group: -
Min:
1 [%]
Description:
Sets the dynamic response factor for speed controller optimization.
After optimization, the dynamic response achieved is displayed in r1968.
Dependency:
See also: p1959, r1968
See also: F07985
Note
For a rotating measurement, this parameter can be used to optimize the speed controller.
p1967 = 100 % --> speed controller optimization according to a symmetric optimum.
p1967 > 100 % --> optimization with a higher dynamic response (Kp higher, Tn lower).
If the actual dynamic response (see r1968) is significantly reduced with respect to the required dynamic response
(p1967), then this can be as a result of mechanical load oscillations. If, in spite of this load behavior, a higher dynamic
response is required, then the oscillation test (p1959.4 = 0) should be deactivated and the measurement repeated.
r1968

Speed_ctrl_opt dynamic factor actual / n_opt dyn_fact act

Access level: 3
Can be changed: -
Unit group: -
Min:
- [%]
Description:
Displays the dynamic factor which is actually achieved for the vibration test
Dependency:
See also: p1959, p1967
See also: F07985
Note
This dynamic factor only refers to the control mode of the speed controller set in p1960.
p1980[0...n]

PolID technique / PolID technique

Access level: 3
Can be changed: T, U
Unit group: -
Min:
1
Description:
Sets the pole position identification technique.
p1980 = 1, 8: The current magnitude is set using p0329.
p1980 = 4, 6: The current magnitude of the first measurement section is set using p0325, the second using p0329.
p1980 = 10: The rated motor current is impressed to align.
The current magnitudes are limited to the rated power unit values.
Value:
1:
4:
6:
8:
10:
Dependency:
See also: p1780
See also: F07969
550
Voltage pulsing 1st harmonics
Voltage pulsing 2-stage
Voltage pulsing 2-stage inverse
Voltage pulsing 2nd harmonic, inverse
DC current injection
Calculated: CALC_MOD_ALL Data type: FloatingPoint32
Scaling: -
Unit selection: -
Max:
400 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
- [%]
Calculated: CALC_MOD_REG Data type: Integer16
Scaling: -
Unit selection: -
Max:
10
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Dynamic index: -
Function diagram: -
Factory setting:
100 [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
- [%]
Dynamic index: MDS, p0130
Function diagram: -
Factory setting:
4