Parameters
7.3 Parameters
01
02
03
04
05
06
07
08
09
10
NOTICE
The master control only influences control word 1 and speed setpoint 1. Other control word/setpoints can be
transferred from another automation device.
Note
OC: Operating condition
p2040
Fieldbus interface monitoring time / Fieldbus t_monit
Access level: 3
Can be changed: T, U
Unit group: -
Min:
0 [ms]
Description:
Sets the monitoring time to monitor the process data received via the fieldbus interface.
If no process data is received within this time, then an appropriate message is output.
Dependency:
See also: F01910
Note
p2040 = 0:
Monitoring is deactivated.
For p2030 = 2 (Modbus RTU) or p2030 = 5 (BACnet MS/TP) the following deviation applies:
Factory setting: 10000
r2050[0...11]
CO: PROFIdrive PZD receive word / PZD recv word
Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Connector output to interconnect PZD (setpoints) with word format received from the fieldbus controller.
562
OC / OFF2
OC / OFF3
Enable operation
Enable ramp-function generator
Start ramp-function generator
Enable speed setpoint
Acknowledge fault
Jog bit 0
Jog bit 1
Master control by PLC
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max:
1999999 [ms]
Calculated: -
Scaling: 4000H
Unit selection: -
Max:
-
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
No
-
No
-
No
-
No
-
No
-
No
-
No
-
No
3030
No
3030
No
-
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9310
Factory setting:
1000 [ms]
Data type: Integer16
Dynamic index: -
Function diagram: 2440, 2468,
9360
Factory setting:
-
SINAMICS G120XA converter