Wiring
4.2 Control interfaces
Default setting 43: "2 pumps with analog control"
Default setting
Procedure with the BOP-2 operator panel:
→ SETUP → ... → MAc PAr → P15 = X AI 2XP → ... → FINISH
86
Setting Parameter
p0015 = 43
43
AI 0 p2253[0] =
755[0]
p1070[0] =
755[0]
AI 1 p2264[0] =
755[1]
AO 0 p0771[0] = 21
AO 1 p0771[1] = 27
Characteristics
Multi-pump con‐
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Setting Parameter
DI 0
p29652[0] = 722.0
p29650[0] = 0
ON/OFF1
p0840[0] = 29659.0
OFF2
p0844[0] = 29659.1
DI 1
p29543[0] = 722.1
DI 2
p29543[1] = 722.2
DI 4
p2200 = 722.4
DI 5
p2104[0] = 722.5
p29520 = 1
trol
p29521 = 2
p29539 = 1
p29540 = 1
DO 0
p0730 = 52.3
DO 1
p0731 = 52.2
DO 2
p0732 = 29529.0
DO 3
p0733 = 29529.1