Technical data

11.4 Technical data dependent on the power

11.4
Technical data dependent on the power
Frame
Rated power
size
(kW)
Based on Low Overload
FSA
0.75
1.1
1.5
2.2
3
FSB
4
5.5
7.5
FSC
11
15
FSD
18.5
22
30
37
45
FSE
55
FSF
75
90
110
132
FSG
160
200
250
FSH
315
355
400
FSJ
450
500
560
866
Rated input
Rated output
current (A)
current (A)
2.1
2.2
2.8
3.1
3.6
4.1
5.3
5.6
6.6
7.3
8.5
8.8
11.5
12.5
15.8
16.5
25.8
25
28.5
31
41
37
46
43
56
58
73
68
84
82.5
106
103
143
136
164
164
200
201
234
237
278
289
348
364
417
436
617
590
684
645
760
725
870
820
959
895
1060
1015
Power loss (kW)
Without filter
With filter
0.043
0.043
0.055
0.055
0.071
0.072
0.085
0.086
0.116
0.117
0.118
0.119
0.172
0.175
0.225
0.231
0.306
0.31
0.387
0.402
0.54
0.54
0.63
0.64
0.92
0.93
0.97
0.98
1.26
1.27
1.56
1.57
1.72
1.74
2.16
2.18
2.27
2.29
2.86
2.89
--
3.66
--
4.51
--
5.44
--
6.4
--
7.29
--
7.99
--
9
--
10
--
11.2
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Net weight (kg)
Without filter
With filter
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
3.1
3.4
5.9
6.2
5.9
6.2
5.9
6.2
7.2
7.7
7.2
7.7
16.2
17.9
16.2
17.9
16.2
17.9
18.4
19.1
16.6
18.3
27
27
60.3
66.8
60.3
66.8
64
68.3
64
68.3
--
105
--
113
--
120
--
132
--
134
--
137
--
204
--
210
--
218
SINAMICS G120XA converter