Note
The parameter is not influenced by setting the factory setting.
p2016[0...3]
CI: Comm IF USS PZD send word / Comm USS send word
Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Selects the PZD (actual values) to be sent via the commissioning interface USS.
The actual values are displayed on an intelligent operator panel (IOP).
Index:
[0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
p2020
Field bus interface baud rate / Field bus baud
Access level: 2
Can be changed: T
Unit group: -
Min:
4
Description:
Sets the baud rate for the field bus interface (RS485).
Value:
4:
5:
6:
7:
8:
9:
10:
11:
12:
13:
Note
Fieldbus IF: Fieldbus interface
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
The parameter is set to the factory setting when the protocol is reselected.
When p2030 = 1 (USS), the following applies:
Min./max./factory setting: 4/13/8
For p2030 = 2 (Modbus RTU), the following applies:
Min./max./factory setting: 5/13/7
For p2030 = 5 (BACnet MS/TP) the following applies:
Possible values/factory setting: (6, 7, 8, 10) / 8
If p2030 = 8 (P1), the following applies:
Min./max./factory setting: 5/7/5
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
2400 baud
4800 baud
9600 baud
19200 baud
38400 baud
57600 baud
76800 baud
93750 baud
115200 baud
187500 baud
Calculated: -
Scaling: 4000H
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
13
Parameters
7.3 Parameters
Data type: Unsigned32 /
Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0
Data type: Integer16
Dynamic index: -
Function diagram: 9310
Factory setting:
8
555