Dependency:
The parameter is preset when commissioning the system for the first time and for the factory setting, depending on the
power unit that is connected.
Depending on the setting, the ability to see control parameters is restricted depending on the particular application.
The following applies for p0096 > 0:
The motor data identification routine is preset (p1900 = 2).
The following applies for p0096 = 1:
The motor type (p0300) synchronous or reluctance motor is not possible.
Note
When changing p0096 to 1 or 2, when completing commissioning, fast parameterization should be executed (p3900
> 0).
Depending on the setting, after quick commissioning and/or automatic parameterization, the procedure for motor data
identification as well as the setting of the operating mode and parameterization of the closed-loop control must be
appropriately adapted.
p0096
Application class / Appl_class
CUG120XA_USS
Access level: 1
(PM330)
Can be changed: C2(1)
Unit group: -
Min:
0
Description:
Setting the commissioning and control view for various application classes.
Value:
0:
2:
Dependency:
The parameter is preset when commissioning the system for the first time and for the factory setting, depending on the
power unit that is connected.
Depending on the setting, the ability to see control parameters is restricted depending on the particular application.
The following applies for p0096 > 0:
The motor data identification routine is preset (p1900 = 2).
Note
When changing p0096 to 1 or 2, when completing commissioning, fast parameterization should be executed (p3900
> 0).
Depending on the setting, after quick commissioning and/or automatic parameterization, the procedure for motor data
identification as well as the setting of the operating mode and parameterization of the closed-loop control must be
appropriately adapted.
p0100

IEC/NEMA Standards / IEC/NEMA Standards

Access level: 1
Can be changed: C2(1, 2)
Unit group: -
Min:
0
Description:
Defines whether the motor and drive converter power settings (e.g. rated motor power, p0307) are expressed in [kW]
or [hp].
Depending on the selection, the rated motor frequency (p0310) is either set to 50 Hz or 60 Hz.
For p0100 = 0, 2, the following applies: The power factor (p0308) should be parameterized.
For p0100 = 1, the following applies: The efficiency (p0309) should be parameterized.
Value:
0:
1:
2:
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Expert
Dynamic Drive Control (DDC)
IEC (50 Hz line, SI units)
NEMA (60 Hz line, US units)
NEMA (60 Hz line, SI units)
Calculated: -
Scaling: -
Unit selection: -
Max:
2
Calculated: -
Scaling: -
Unit selection: -
Max:
2
Parameters
7.3 Parameters
Data type: Integer16
Dynamic index: -
Function diagram: 6019
Factory setting:
0
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0
375