Operating The Converter On A Tn Line System; Tt System - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Wiring
4.1 Line supply and motor
A TN system transfers the PE protective conductor to the installed plant or system using a cable.
Generally, in a TN system the neutral point is grounded. There are versions of a TN system with
a grounded line conductor, e.g. with grounded L1.
The TN system can transfer the neutral conductor N and the PE protective conductor either
separately or combined.

Operating the converter on a TN line system

Table 4-1
Converter
Frame size
Without line filter
Integrated line filter C3
✓ = Operation permissible
Operation permissible once grounding screw has been removed
1)
If the grounding screw has been removed, the converter no longer fulfills the requirements of class C3.
- Operation not permissible
○ Converter not available
More information on removing the grounding connection in the converter:
4.1.1.2

TT system

Overview
Figure 4-2
In a TT system, the transformer grounding and the installation grounding are independent of
one another.
There are TT supplies where the neutral conductor N is either transferred – or not.
58
Converter operated on a TN system
A
Removing functional grounding of the converter (Page 60)
TT system
Line supply with grounded neutral
B
C
D
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
E
F
G
SINAMICS G120XA converter
H
J