Multi-pump control switch-in threshold / Mpc sw_in thr

Access level: 3
Can be changed: T, U
Unit group: 9_1
Min:
0.0 [%]
Description:
Theshold value for the delayed swithcing-in or switching-out of motors.
Motor switching-in is activated if the maximum speed is reached and the wait time in p29524 has expired.
Dependency:
refer to P29524
p29524

Multi-pump control switch-in delay / Mpc_ctrl t_in_del

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0 [s]
Description:
Additional delay time for staging motors after the system deviation of the technology controller has exceeded the
threshold value p29523 and the motor has reachede the maximum speed.
Dependency:
refer to P29523
Note
If the deviation at the technology controller input exceeds the overcontrol threshold p29526, the delay time is bypassed.
p29525

Multi-pump control switch-out delay / Mpc sw_out del

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0 [s]
Description:
Additional delay time for switch-out motor after the system deviation of the technology controller has exceeded the
threshold p29523 and the motor has reached the speed threshold p1080+P29528.
Dependency:
Refer to P29523,P29526
Note
If the deviation at the technology controller input exceeds the overcontrol threshold p29526, the delay time is bypassed.
If the hibernation mode is active, ensure that p2391 is longer than p29525 to avoid false operation of hibernation.
p29526

Multi-pump control overcontrol threshold / Mpc overctrl thr

Access level: 3
Can be changed: T, U
Unit group: 9_1
Min:
0.0 [%]
Description:
Sets the threshold value for instaneous switching-in or switching-out motors.
Note
If the PID error rises above the multi-pump control overcontrol threshold p29526, the inverter skips the switch-in delay
time and performs the switch-in operation immediately.
If the PID error drops below the multi-pump control overcontrol threshold -p29526, the inverter skips the switch-out
delay and performs the switch-out operation immediately.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max:
200.0 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
650 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
650 [s]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max:
200.0 [%]
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
20.0 [%]
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
30 [s]
Data type: Unsigned16
Dynamic index: -
Function diagram: -
Factory setting:
30 [s]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
25.0 [%]
707