Motor Stator Leakage Inductance / Mot L_Stator Leak.; Motor Stator Inductance D Axis / Mot L_Stator D; Motor Rotor Leakage Inductance / Mot L_Rot Leak - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

NOTICE
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note
The parameter is not used for synchronous motors (p0300 = 2).
p0356[0...n]

Motor stator leakage inductance / Mot L_stator leak.

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.00000 [mH]
Description:
Induction machine: sets the stator leakage inductance of the motor.
Synchronous motor: Sets the stator quadrature axis inductance of the motor.
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identification
routine (p1910).
NOTICE
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note
If the stator leakage inductance (p0356) for induction motors is changed outside the commissioning phase (p0010 >
0), the magnetizing inductance (p0360) is automatically adapted to the new EMF (r0337). You are then advised to
repeat the measurement for the saturation characteristic (p1960).
For permanent-magnet synchronous motors (p0300 = 2), this is the non-saturated value and is, therefore, ideal for a
low current.
For a controlled reluctance motor (p0300 = 6), this is the direct axis stator inductance at the rated operating point.
p0357[0...n]

Motor stator inductance d axis / Mot L_stator d

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.00000 [mH]
Description:
Sets the stator direct-axis inductance of the synchronous motor.
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identification
routine (p1910).
Note
For permanent-magnet synchronous motors (p0300 = 2), this is the non-saturated value and is ideal for a low current.
For a controlled reluctance motor (p0300 = 6), this is the direct axis stator inductance at the rated operating point.
p0358[0...n]

Motor rotor leakage inductance / Mot L_rot leak

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.00000 [mH]
Description:
Sets the rotor/secondary section leakage inductance of the motor.
The value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identification routine
(p1910).
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: CALC_MOD_EQU Data type: FloatingPoint32
Scaling: -
Unit selection: -
Max:
1000.00000 [mH]
Calculated: CALC_MOD_EQU Data type: FloatingPoint32
Scaling: -
Unit selection: -
Max:
1000.00000 [mH]
Calculated: CALC_MOD_EQU Data type: FloatingPoint32
Scaling: -
Unit selection: -
Max:
1000.00000 [mH]
Parameters
7.3 Parameters
Dynamic index: MDS, p0130
Function diagram: -
Factory setting:
0.00000 [mH]
Dynamic index: MDS, p0130
Function diagram: -
Factory setting:
0.00000 [mH]
Dynamic index: MDS, p0130
Function diagram: 6727
Factory setting:
0.00000 [mH]
403