p3327[0...n]

Fluid flow machine speed point 4 / Fluid_mach n4

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the speed (n) of point 4 as a [%].
Dependency:
See also: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3328, p3329
Note
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3328[0...n]

Fluid flow machine power point 5 / Fluid_mach P5

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the power (P) of point 5 as a [%].
Dependency:
See also: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3327, p3329
Note
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3329[0...n]

Fluid flow machine speed point 5 / Fluid_mach n5

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the speed (n) of point 5 as a [%].
Dependency:
See also: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3327, p3328
Note
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3330[0...n]

BI: 2/3 wire control command 1 / 2/3 wire cmd 1

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the signal source for command 1 for the two-wire control/three-wire control.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: -
Unit selection: -
Max:
100.00
Calculated: -
Scaling: -
Unit selection: -
Max:
100.00
Calculated: -
Scaling: -
Unit selection: -
Max:
100.00
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
75.00
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
100.00
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
100.00
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2272, 2273
Factory setting:
0
647