Cu Analog Inputs Characteristic Value X1 / Cu Ai Char X1 - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Description:
Sets the type of analog inputs.
p0756[0...1] = 0, 1, 4 corresponds to a voltage input (r0752, p0757, p0759 are displayed in V).
p0756[0...2] = 2, 3 corresponds to a current input (r0752, p0757, p0759 are displayed in mA).
p0756[2...3] = 6, 7, 10 corresponds to a resistor input for temperature measurement (r0752, p0757, p0759 are
displayed in °C).
p0756[2...3] = 8 No temperature sensor connected. Mode for deactivating sensor monitoring (alarm A03520).
Value:
0:
1:
2:
3:
4:
Index:
[0] = AI0 (X131 3/4)
[1] = AI1 (X131 10/11)
[2] = Reserved
[3] = Reserved
Dependency:
See also: A03520
WARNING
The maximum voltage difference between analog input terminals AI+, AI-, and the ground must not exceed 35 V.
If the system is operated when the load resistor is switched on, the voltage between differential inputs AI+ and AI- must
not exceed 10 V or the injected 80 mA current otherwise the input will be damaged.
Note
When changing p0756, the parameters of the scaling characteristic (p0757, p0758, p0759, p0760) are overwritten with
the following default values:
For p0756 = 0, 4, p0757 is set to 0.0 V, p0758 = 0.0 %, p0759 = 10.0 V and p0760 = 100.0 %.
For p0756 = 1, p0757 is set to 2.0 V, p0758 = 0.0 %, p0759 = 10.0 V and p0760 = 100.0 %.
For p0756 = 2, p0757 is set to 0.0 mA, p0758 = 0.0 %, p0759 = 20.0 mA and p0760 = 100.0 %.
For p0756 = 3, p0757 is set to 4.0 mA, p0758 = 0.0 %, p0759 = 20.0 mA and p0760 = 100.0 %.
For p0756 = 6, 7, p0757 is set to 0 °C, p0758 = 0.0 %, p0759 = 100 °C and p0760 = 100.0 %.
p0757[0...3]

CU analog inputs characteristic value x1 / CU AI char x1

Access level: 2
Can be changed: T, U
Unit group: -
Min:
-50.000
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (V, mA, °C) of the 1st value pair of the characteristic.
Index:
[0] = AI0 (X131 3/4)
[1] = AI1 (X131 10/11)
[2] = Reserved
[3] = Reserved
Note
The parameters for the characteristic do not have a limiting effect.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Unipolar voltage input (0 V ... +10 V)
Unipolar voltage input monitored (+2 V ... +10 V)
Unipolar current input (0 mA ... +20 mA)
Unipolar current input monitored (+4 mA to +20 mA)
Bipolar voltage input (-10 V ... +10 V)
Calculated: -
Scaling: -
Unit selection: -
Max:
160.000
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9566, 9568,
9576
Factory setting:
0.000