A07994 (F, N) Drive: motor data identification not performed

Reaction:
NONE
Acknowledge:
NONE
Cause:
The "Vector control" mode or application class "Standard Drive Control, STC" (p0096 = 1) has been selected, and a motor
data identification has still not been performed.
The alarm is initiated when changing the drive data set (see r0051) in the following cases:
- vector control is parameterized in the actual drive data set (p1300 >= 20).
and
- motor data identification has still not been performed in the actual drive data set (see r3925).
Note:
For SINAMICS G120, a check is made and the alarm is output also when exiting commissioning and when the system
powers up.
Remedy:
- Perform motor data identification (see p1900).
- if required, parameterize "U/f control" (p1300 < 20) or set p0096 = 0 (only G120).
- switch over to a drive data set, in which the conditions do not apply.

F08010 (N, A) CU: Analog-to-digital converter

Reaction:
OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The analog-to-digital converter on the Control Unit has not supplied any converted data.
Remedy:
- check the power supply.
- replace Control Unit.

F08501 (N, A) PROFINET: Setpoint timeout

Reaction:
OFF3 (IASC/DCBRK, NONE, OFF1, OFF2, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
The reception of setpoints from PROFINET has been interrupted.
- bus connection interrupted.
- controller switched off.
- controller set into the STOP state.
Remedy:
- Restore the bus connection and set the controller to RUN.
- if the error is repeated, check the update time set in the bus configuration (HW Config).
F08502 (A)

PROFINET: Monitoring time sign-of-life expired

Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The monitoring time for the sign-of-life counter has expired.
The connection to the PROFINET interface was interrupted.
Remedy:
- carry out a POWER ON (switch-off/switch-on).
- contact Technical Support.
A08511 (F)
PROFINET: Receive configuration data invalid
Reaction:
NONE
Acknowledge:
NONE
Cause:
The drive unit did not accept the receive configuration data.
Alarm value (r2124, interpret decimal):
Return value of the receive configuration data check.
2: Too many PZD data words for input or output. The number of possible PZD is specified by the number of indices in r2050/
p2051.
3: Uneven number of bytes for input or output.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Warnings, faults and system messages
9.6 List of fault codes and alarm codes
805