Flow Characteristic; Factory Setting Of The Flow Characteristic - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Flow characteristic

Figure 6-93
To set the characteristic, you require the following data from the machine manufacturer for each
speed interpolation point:
● The flow rate of the fluid-flow machine associated with the 5 selected converter speeds
● At constant speed, the power drawn which is associated with the 5 flow rates corresponds
to the line frequency and mechanical throttling of the flow rate.
Parameters
Number
r0039[0...n]
p0040
r0041
r0042[0...n]
p0043
p3320[0...n]
p3321[0...n]
p3322[0...n]
p3323[0...n]
p3324[0...n]
p3325[0...n]
p3326[0...n]
p3327[0...n]
p3328[0...n]
p3329[0...n]
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB

Factory setting of the flow characteristic

Name
CO: Energy display
Reset energy consumption display
Energy saved
CO: Process energy display
BI: Energy consumption display enabled.
Fluid flow machine power, point 1
Fluid flow machine speed, point 1
Fluid flow machine power, point 2
Fluid flow machine speed, point 2
Fluid flow machine power, point 3
Fluid flow machine speed, point 3
Fluid flow machine power, point 4
Fluid flow machine speed, point 4
Fluid flow machine power, point 5
Fluid flow machine speed, point 5
Advanced commissioning
6.9 Energy saving
Factory setting
-
0
-
-
0
25
0
50
25
77
50
92
75
100
100
345