Bi: Enable Setpoint/Inhibit Setpoint / Setpoint Enable; Bi: Ramp-Function Generator, Accept Setting Value / Rfg Accept Set V - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

NOTICE
The ramp-function generator is, independent of the state of the signal source, active in the following cases:
- OFF1/OFF3.
- ramp-function generator output within the suppression bandwidth.
- ramp-function generator output below the minimum speed.
p1142[0...n]

BI: Enable setpoint/inhibit setpoint / Setpoint enable

Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source for the command "enable setpoint/inhibit setpoint".
For the PROFIdrive profile, this command corresponds to control word 1 bit 6 (STW1.6).
BI: p1142 = 0 signal
Inhibits the setpoint (the ramp-function generator input is set to zero).
BI: p1142 = 1 signal
Setpoint enable.
Dependency:
See also: p1140, p1141
CAUTION
When "master control from PC" is activated, this binector input is ineffective.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note
When the function module "position control" (r0108.3 = 1) is activated, this binector input is interconnected as follows
as standard:
BI: p1142 = 0 signal
p1143[0...n]

BI: Ramp-function generator, accept setting value / RFG accept set v

Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source for accepting the setting value of the ramp-function generator.
Dependency:
The signal source for the ramp-function generator setting value is set using parameters.
See also: p1144
Note
0/1 signal:
The ramp-function generator output is immediately (without delay) set to the setting value of the ramp-function
generator.
1 signal:
The setting value of the ramp-function generator is effective.
1/0 signal:
The input value of the ramp-function generator is effective. The ramp-function generator output is adapted to the input
value using the ramp-up time or the ramp-down time.
0 signal:
The input value of the ramp-function generator is effective.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Parameters
7.3 Parameters
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 2501
Factory setting:
1
Data type: Unsigned32 / Binary
Dynamic index: CDS, p0170
Function diagram: 3070
Factory setting:
29640.0
487