Multi-Pump Control Continunous Operating Hours / Mpc Conti_Oper_Hrs; Co/Bo: Multi-Pump Control Feedback Signal For Contactor; Ramp-Up Scaling 1 / Rmpupscaling1; Threshold Speed 2 / Thresh_2_Ramp - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Parameters
7.3 Parameters
p29547[0...3]

Multi-pump control continunous operating hours / Mpc Conti_oper_hrs

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.00 [h]
Description:
Displays the continuous operating hours for the motors.
The display can only be reset to zero.
Index:
[0] = motor 1 operating hours
[1] = motor 2 operating hours
[2] = motor 3 operating hours
[3] = motor 4 operating hours
Note
Continuous operation is measured starting from when a motor is ON. It ends when a motor is OFF.
r29549
CO/BO: Multi-pump control feedback signal for contactor / Mpc fdb signal
Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Bico to p1269[0] as a feedback signal
p29570[0...n]

Ramp-up scaling 1 / RmpUpScaling1

Access level: 3
Can be changed: T
Unit group: -
Min:
0.00 [%]
Description:
Sets the ramp-up scaling 1 for the dual ramp function [%].
p29571[0...n]

Threshold speed 2 / Thresh_2_Ramp

Access level: 3
Can be changed: T
Unit group: 3_1
Min:
0.00 [rpm]
Description:
Defines the threshold 2 for comparing the speed actual value with the speed threshold.
p29572[0...n]
Ramp-up scaling 2 / RmpUpScaling2
Access level: 3
Can be changed: T
Unit group: -
Min:
0.00 [%]
Description:
Sets the ramp-up scaling 2 for the dual ramp function [%].
712
Calculated: -
Scaling: -
Unit selection: -
Max:
1000000.00 [h]
Calculated: -
Scaling: -
Unit selection: -
Max:
-
Calculated: -
Scaling: -
Unit selection: -
Max:
9999999.00 [%]
Calculated: -
Scaling: p2000
Unit selection: p0505
Max:
210000.00 [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max:
9999999.00 [%]
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
0.00 [h]
Data type: Unsigned32
Dynamic index: -
Function diagram: -
Factory setting:
-
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
100.00 [%]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
30.00 [rpm]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
100.00 [%]
SINAMICS G120XA converter

Advertisement

Table of Contents
loading

Table of Contents