7.3 Parameters
p29631[0...4]

Flow meter pump power / FlowM_power

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.00 [kW]
Description:
Determines the power points for flow estimation.
Five power values are put into the indexes of this parameter. These values should be spread across the full power
range of the inverter.
User should guarantee values in all indexes is increasing in sequence (p29631[0] <= p29631 [1] <= p29631[2] <= ...).
Otherwise the calculated flow value will be 0.
p29632[0...4]

Flow meter pump flow / FlowM_flow

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.00 [m³/h]
Description:
Determines the flow for the corresponding pump power point used for flow estimation.
Five correcponding flow values should be entered derived from the manufacturer's pump characteristic curve.
r29633

Flow meter calculated flow / FlowM_calc flow

Access level: 3
Can be changed: -
Unit group: -
Min:
- [m³/h]
Description:
The calculation result of flow meter.
r29640.0...18

CO/BO: Extented setpoint channel selection output / Setp selection

Access level: 3
Can be changed: -
Unit group: -
Min:
-
Description:
Displays the actual output of the extended setpoint channel selection.
Bit field:
Bit
00
01
03
04
05
06
16
17
18
720
Signal name
Extend speed setpoint selected
Frost or condensation executing
Deragging executing
Pipe filling executing
Total executing
Normal executing
Ramp up status
Ramp down status
Target setpoint reached flag
Calculated: -
Scaling: -
Unit selection: -
Max:
340.28235E36 [kW]
Calculated: -
Scaling: -
Unit selection: -
Max:
340.28235E36 [m³/h]
Calculated: -
Scaling: -
Unit selection: -
Max:
- [m³/h]
Calculated: -
Scaling: -
Unit selection: -
Max:
-
1 signal
1
1
1
1
1
1
1
1
1
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
0.00 [kW]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
0.00 [m³/h]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
- [m³/h]
Data type: Unsigned32
Dynamic index: -
Function diagram: -
Factory setting:
-
0 signal
FP
0
-
0
-
0
-
0
-
0
-
0
-
0
-
0
-
0
-
SINAMICS G120XA converter

Advertisement

Table of Contents
loading

Table of Contents