Rotating Measurement Selection / Rot Meas Sel - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

Parameters
7.3 Parameters
03
04
11
12
13
14
Dependency:
See also: F07988
Note
The following parameters are influenced for the individual optimization steps:
Bit 01: p0320, p0360, p0362 ... p0369
Bit 02: p0341, p0342
Bit 03: p1400.0, p1458, p1459, p1463, p1470, p1472, p1496
Bit 04: Dependent on p1960
p1960 = 1, 3: p1400.0, p1458, p1459, p1470, p1472, p1496
For bit 12 = 1:
The selection only has an effect on the measurement p1960 = 1. For the shortened measurement, the magnetizing
current and moment of inertia are determined with a somewhat lower accuracy.
p1960

Rotating measurement selection / Rot meas sel

Access level: 3
Can be changed: T
Unit group: -
Min:
0
Description:
Sets the rotating measurement.
The rotating measurement is carried out after the next switch-on command.
The setting possibilities of the parameter depend on the open-loop/closed-loop control mode (p1300).
p1300 < 20 (U/f open-loop control):
It is not possible to select rotating measurement or speed controller optimization.
p1300 = 20, 22 (encoderless operation):
Only rotating measurement or speed controller optimization can be selected in the encoderless mode.
Value:
0:
1:
3:
Dependency:
Before the rotating measurement is carried out, the motor data identification routine (p1900, p1910, r3925) should
have already been done.
When selecting the rotating measurement, the drive data set changeover is suppressed.
See also: p1300, p1900, p1959, p1967, r1968
DANGER
For drives with a mechanical system that limits the distance moved, it must be ensured that this is not reached during
the rotating measurement. If this is not the case, then it is not permissible that the measurement is carried out.
NOTICE
To permanently accept the determined settings they must be saved in a non-volatile fashion (p0971).
During the rotating measurement it is not possible to save the parameter (p0971).
Note
When the rotating measurement is activated, it is not possible to save the parameters (p0971).
Parameter changes are automatically made for the rotating measurement (e.g. p1120); this is the reason that up to the
end of the measurement, and if no faults are present, no manual changes should be made.
The ramp-up and ramp-down times (p1120, p1121) are limited, for the rotating measurement, to 900 s.
548
Re-calculates the speed controller parameters
Speed controller optimization (vibration test)
Do not change the controller parameters during the
measurement
Measurement shortened
After measurement direct transition into operation
Calculate speed actual value smoothing time
Inhibited
Rotating measurement in encoderless operation
Speed controller optimization in encoderless operation
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max:
3
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
No
-
No
-
No
-
No
-
No
-
No
-
Data type: Integer16
Dynamic index: -
Function diagram: -
Factory setting:
0
SINAMICS G120XA converter

Advertisement