7.3 Parameters
r2273

CO: Technology controller system deviation / Tec_ctrl sys_dev

Access level: 2
Can be changed: -
Unit group: 9_1
Min:
- [%]
Description:
Displays the system deviation between the setpoint and actual value of the technology controller.
Dependency:
See also: p2263
p2274
Technology controller differentiation time constant / Tec_ctrl D comp T
Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the time constant for the differentiation (D component) of the technology controller.
Note
p2274 = 0: Differentiation is disabled.
p2280

Technology controller proportional gain / Tec_ctrl Kp

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000
Description:
Sets the proportional gain (P component) of the technology controller.
Note
p2280 = 0: The proportional gain is disabled.
p2285

Technology controller integral time / Tec_ctrl Tn

Access level: 2
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the integral time (I component, integrating time constant) of the technology controller.
NOTICE
The following applies for p2251 = 0:
If the output of the technology controller lies within the range of a suppression (skip) bandwidth (p1091 ... p1094,
p1101) or below the minimum speed (p1080), the integral component of the controller is held so that the controller
temporarily works as a P controller. This is necessary in order to prevent the controller from behaving in an unstable
manner, as the ramp-function generator switches to the parameterized up and down ramps (p1120, p1121) at the
same time in order to avoid setpoint steps. This state can be exited or avoided by changing the controller setpoint or
by using the start speed (= minimum speed).
Note
When the controller output reaches the limit, the I component of the controller is held.
p2285 = 0:
The integral time is disabled and the I component of the controller is reset.
616
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max:
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
60.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
1000.000
Calculated: -
Scaling: -
Unit selection: -
Max:
10000.000 [s]
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7958
Factory setting:
- [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7958
Factory setting:
0.000 [s]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7958
Factory setting:
0.500
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 7958
Factory setting:
10.000 [s]
SINAMICS G120XA converter