Off3 Initial Rounding-Off Time / Rfgoff3 T_Strt_Rnd; Off3 Final Rounding-Off Time / Rfg Off3 T_End_Del; Ci: Ramp-Function Generator Ramp-Up Time Scaling / Rfg T_Ru Scal - Siemens SINAMICS G120XA Operating Instructions Manual

Table of Contents

Advertisement

p1135[0...n]
OFF3 ramp-down time / OFF3 t_RD
CUG120XA_USS
Access level: 2
(PM330)
Can be changed: C2(1), T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the ramp-down time from the maximum speed down to zero speed for the OFF3 command.
Dependency:
The parameter is pre-assigned depending on the size of the power unit.
Note
This time can be exceeded if the DC link voltage reaches its maximum value.
p1136[0...n]

OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the initial rounding-off time for OFF3 for the extended ramp generator.
p1136[0...n]
OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
CUG120XA_USS
Access level: 3
(PM330)
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the initial rounding-off time for OFF3 for the extended ramp generator.
p1137[0...n]

OFF3 final rounding-off time / RFG OFF3 t_end_del

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0.000 [s]
Description:
Sets the final rounding-off time for OFF3 for the extended ramp generator.
p1138[0...n]

CI: Ramp-function generator ramp-up time scaling / RFG t_RU scal

Access level: 3
Can be changed: T
Unit group: -
Min:
-
Description:
Sets the signal source for scaling the ramp-up time of the ramp-function generator.
Dependency:
See also: p1120
Note
The ramp-up time is set in p1120.
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Calculated: -
Scaling: -
Unit selection: -
Max:
5400.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
30.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
30.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max:
30.000 [s]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max:
-
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 3070
Factory setting:
3.000 [s]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 3070
Factory setting:
0.000 [s]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 3070
Factory setting:
0.500 [s]
Data type: FloatingPoint32
Dynamic index: DDS, p0180
Function diagram: 3070
Factory setting:
0.000 [s]
Data type: Unsigned32 /
FloatingPoint32
Dynamic index: CDS, p0170
Function diagram: 3070
Factory setting:
1
485

Advertisement

Table of Contents
loading

Table of Contents