p1274[0...1]

Bypass switch monitoring time / Switch t_monit

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0 [ms]
Description:
Sets the monitoring time for the bypass switch.
Index:
[0] = Switch motor/drive
[1] = Switch motor/line supply
Dependency:
The "Bypass" function is only available for induction motors.
Note
The monitoring is deactivated with p1274 = 0 ms.
The changeover time for the bypass (p1262) is extended by the value in this parameter.
p1280[0...n]

Vdc controller configuration (U/f) / Vdc_ctr config U/f

Access level: 3
Can be changed: T, U
Unit group: -
Min:
0
Description:
Sets the configuration of the controller for the DC link voltage (Vdc controller) in the U/f operating mode.
Value:
0:
1:
2:
3:
Note
For high input voltages (p0210), the following settings can improve the degree of ruggedness of the Vdc_max controller:
- set the input voltage as low as possible, and in so doing, avoid A07401 (p0210).
- set the rounding times (p1130, p1136).
- increase the ramp-down times (p1121).
- reduce the integral time of the controller (p1291), factor 0.5.
- activate the Vdc correction in the current controller (p1810.1 = 1) or reduce the derivative action time of the controller
(p1292, factor 0.5).
In this case, we generally recommend to use vector control (p1300 = 20) (Vdc controller, see p1240).
The following measures are suitable to improve the Vdc_min controller:
- Optimize the Vdc_min controller (see p1287).
- Activate the Vdc correction in the current controller (p1810.1 = 1).
p1281[0...n]

Vdc controller configuration / Vdc ctrl config

Access level: 3
Can be changed: T, U
Unit group: -
Min:
-
Description:
Sets the configuration for the DC link voltage controller.
Bit field:
Bit
00
02
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Inhibit Vdc ctrl
Enable Vdc_max controller
Enable Vdc_min controller (kinetic buffering)
Enable Vdc_min controller and Vdc_max controller
Signal name
Vdc min control (U/f) without up ramp
Vdc min shorter wait time when the line returns
Calculated: -
Scaling: -
Unit selection: -
Max:
5000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max:
3
Calculated: CALC_MOD_ALL Data type: Unsigned16
Scaling: -
Unit selection: -
Max:
-
1 signal
Yes
Yes
Parameters
7.3 Parameters
Data type: FloatingPoint32
Dynamic index: -
Function diagram: -
Factory setting:
1000 [ms]
Data type: Integer16
Dynamic index: DDS, p0180
Function diagram: 6300, 6320,
6854
Factory setting:
1
Dynamic index: DDS, p0180
Function diagram: -
Factory setting:
0000 bin
0 signal
FP
No
-
No
-
505