7.3 Parameters
p0758[0...3]

CU analog inputs characteristic value y1 / CU AI char y1

Access level: 2
Can be changed: T, U
Unit group: -
Min:
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 1st value pair of the characteristic.
Index:
[0] = AI0 (X131 3/4)
[1] = AI1 (X131 10/11)
[2] = Reserved
[3] = Reserved
Note
The parameters for the characteristic do not have a limiting effect.
p0759[0...3]

CU analog inputs characteristic value x2 / CU AI char x2

Access level: 2
Can be changed: T, U
Unit group: -
Min:
-50.000
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (V, mA, °C) of the 2nd value pair of the characteristic.
Index:
[0] = AI0 (X131 3/4)
[1] = AI1 (X131 10/11)
[2] = Reserved
[3] = Reserved
Note
The parameters for the characteristic do not have a limiting effect.
p0760[0...3]

CU analog inputs characteristic value y2 / CU AI char y2

Access level: 2
Can be changed: T, U
Unit group: -
Min:
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
434
Calculated: -
Scaling: -
Unit selection: -
Max:
1000.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max:
160.000
Calculated: -
Scaling: -
Unit selection: -
Max:
1000.00 [%]
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9566, 9568,
9576
Factory setting:
0.00 [%]
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9566, 9568,
9576
Factory setting:
[0] 10.000
[1] 10.000
[2] 20.000
[3] 100.000
Data type: FloatingPoint32
Dynamic index: -
Function diagram: 9566, 9568,
9576
Factory setting:
100.00 [%]
SINAMICS G120XA converter